SharpEye Flame Detector

Are you compliant with European standard EN54-10

We are pleased to present our new flame detector range. SharpEye is compliant with the new European standard, which took effect on 1st December. SharpEye detectors are specifically designed for all fire types. Their capabilities to analyze spectrums give them a high level of reliability.

Operating

Optical technology enables SharpEye to sense radiation dispersed by flames and the by-products of combustion. Depending on the model, SharpEye can use one or several sensors, either in UV, in IR or a combination of both.

A new range offering brand new features:

  • Compliant with European standard EN54-10
  • SIL2 Approved by TUV according to IEC 61508
  • Ex Approved for Zone 1 hazardous area location (ATEX, IECEx, FM, CSA)
  • High false alarm immunity
  • New compact, lighter design, 100% stainless steel
  • Multiple output options : mA, relays, RS 485 ModBus, Hart
  • Automatic built-in test and dirty optics compensation
  • Heated window-for operation in harsh weather conditions
  • Lower power requirements
  • Expanded field of vision: 100° horizontally and 95° vertically

Our detectors

40/40I Model (IR3)

  • Combines three infrared sensors for the detection of hydrocarbon fires up to a distance of 65 meters with a high immunity to false alarms.
  • DNV approval

New: 40/40M Model (IR4)

  • Combines four infrared sensors for the detection of hydrocarbon and hydrogen fires up to a distance of 65 meters with the highest immunity to false alarms

40/40L Model (UV-IR)

  • This detector combines a UV sensor and an IR sensor for the detection of hydrocarbons, hydrogen and metal fire.
  • High Speed response (150m/sec)

Simple IR, mini UV-IR and mini IR3 are also available and our detectors are supplied with tilt mount and weather protection.

Model

40 / 40 I

40 / 40M

40 / 40L

Type:

IR3

IR4

UV-IR

Materials:

Stainless Steel

Sensor:

Pyroelectrical

Field of View:

Horizontal: 100°; Vertical: 95°

Sensitivity range:

Up to 65 m

Up to 65 m

Up to 15 m

BIT:

Yes

Yes

Yes for 40/40
LB version

HART:

Yes

Power supply:

18-32 VDC

Consumption:

Alarm: max 150 mA (200 mA with heated optics)

Output relays:

5 A/ 30 VDC/250 VAC

Operating temperature range:

-50°C to +75°C (-55°C to +85°C optional)

Heated window:

Yes

Approvals:

ATEX and IECEx
Ex II 2GD
Ex de IIB+H2 T5 (-55°C +75°C)
Ex de IIB+H2 T4 (-55°C +85°C)
Ex tD A21 IP66/X7 T 95°C
Ex tD A21 IP66/X7 T 105°C

FM:
(CSA pending)

Class I Div 1. Groups B, C & D
Class II/III Div1, Groups E, F & G

SIL:

SIL2 by TUV according to IEC61508

Weight:

2.5 kg (+1 kg for the tilt mount)

Dimension:

90 mm x 114 mm x 156 mm

Warranty:

5 Years

Atex
CE
CSA
GOST
HART Protocol
IECEx
TUV Rheinland
ATEX ZONE 1