Detectors |
OLCT 20 |
OLC 20 |
Type |
XP transmitter |
IS transmitter |
XP detector |
Gas detection principle |
Catalytic/ Electrochemical |
Electrochemical |
Catalytic |
Detected gases |
Flammable, toxics and oxygen |
Toxics and oxygen |
Flammable |
Measuring range |
See chart inside |
Sensor housing |
Stainless steel type 316 L |
Precalibrated sensor |
yes |
yes |
no |
Power supply at the detector |
15 to 30 VDC (catalytic) 15 to 30 VDC (chemical) |
10 to 26 VDC |
Depending on the detector |
Maximum power consumption |
100 mA (catalytic) 25 mA (chemical) |
25 mA |
Depending on the detector |
Output signal |
4-20 mA |
4-20 mA |
Wheatstone bridge |
Load impedance |
250 Ω (catalytic) Depending on power supply (chemical) |
47 Ω max |
Not applicable |
Wiring |
3 reinforced wires (catalytic) 2 reinforced wires (chemical) |
2 reinforced wires |
3 reinforced wires |
Loop impedance with ISC monitor |
32 Ω (catalytic) (1 km with 1,5 mm2) 128 Ω (chemical) (4 km with 1,5 mm2) |
32 Ω (1 km with 1,5 mm2) |
32 Ω (catalytic) (1 km with 1,5 mm2) |
Wiring connection |
Delivered with a 6mm-diameter cable |
Fastening |
M25 thread to screw or 3/4’’ NPT |
M25 thread to screw or 3/4’’ NPT |
M25 thread to screw With a stirrup or 3/4’’ NPT |
Ingress protection |
IP 66 |
IP 66 |
IP 66 |
Certification |
EEx d IIC T6 II 2 GD INERIS 01 ATEX 0004X |
EEx ia IIC T4 II 1 GD INERIS 01 ATEX 0004X |
EEx d IIC T6 II 2 GD INERIS 01 ATEX 0004X |
CEM mark |
EN 50270 |
EN 50270 |
EN 50270 |
Weight |
800 gr |
800 gr |
Dimensions |
L 130 x D 60 |
L 130 x D 60 |
L 130 x D 60 |
Operating temperature (for electronic) |
-25°C to +60°C |
-25°C to +60°C |
-25°C to +70°C |