OLCT 10 - OLC 10

Designed for use in boiler rooms and parking garages, the OLCT 10 and OLC 10 monitors give you the most cost-effective solution for the continuous monitoring of toxic (OLCT 10) or flammable gases (OLCT 10, OLC 10) and vapors in ambient air. Easy to install and operate, these detectors combined with the MX 15 control unit meet demanding user requirements.

Technical Specifications

 

Model

OLC 10

OLCT 10

Type:

Catalytic bead sensor (pellistor measuring principle)

Size(WxHxD):

118 x 126 x 58 mm

Material:

ABS

IP Rating:

IP 66

Expected lifetime:

> 4 years

Operating temperature:

-10 to +45°C

Operating humidity range:

0% RH to 95% RH

Operating pressure:

80 to 120 kPa

Accuracy:

+/- 3% LEL

Response time:

T50 < 10s, T90 < 20s

Signal output:

Wheatstone Bridge

Normal operation 4-20mA (Fault < 0.5 mA or > 23.2 mA)

Measuring range:

Combustible gases – 0 to 100 % LEL

Carbon Monoxide – 0 to 300 ppm
Nitric Oxide – 0 to 100 ppm
Nitrogen Dioxide – 0 to 30 ppm

Non-ambiguity reading:

Managed by control unit

Set to 23,2 mA if value > 100% LEL according to European standard EN 61779-4
Disable on request when managed by a suitable controller

Settings:
(CSA pending)

On controller

Without opening the enclosure by means of 2 potentiometers for zeroing and spanning
2 mA signal output in maintenance mode
One dedicated connector to get a gas measurement

Power supply:

by controller only

15 to 30 Vdc (nominal 24 Vdc) 1: Iout (signal) 2:0 V 3: +24 Vdc

Consumption:

See user manual of the controller

100 mA max

Cabling:

OLC10: 3-wire, shielded, core size 1,5 mm2, max. cable length 300 m 1 cable-gland M16 (outer 4 to 8 mm)
OLC 10 TWIN: shielded, core size 1,5 mm2, 3-wire to control unit, 4-wire between both sensors, max. cable length 300 m, 2 cable-glands M16 (outer 4 to 8 mm)

3-wire, shielded, core size 1,5 mm2, max. cable length 1 km if connected
with control unit (32 V max in loop)1 cable gland M16 (outer 4 to 8 mm)

Approvals:

Electromagnetic compatibility according to EN 50270
ATEX II 3 G/EEx nA IIC T6

ATEX II 3G/EEx nA IIC T4

Atex
CE
ATEX ZONE 2 (SAUF POUR LA VERSION FRÉON)