AirAware

Industry proven performance combined with a new, low-profile design make the Oldham AirAware™ a logical choice for those critical areas that require continuous monitoring but not the environmental protection of an explosion-proof enclosure. Providing discrete monitoring and enhanced aesthetics for more commercial or institutional settings, the AirAwareTM Series is the ideal solution for reliable, low-cost fixed-point monitoring.

The AirAwareTM can be configured to operate as a monitor with local LED display, a controller with onboard relay switching capability, a transmitter with 4-20 mA or ModBus RTU outputs, or as a transmitter with on-board relays. Each configuration is designed to meet your specific indoor monitoring needs. Every AirAwareTM is equipped with electrochemical sensing technology, dual alarm LEDs, a digital display providing real-time readings, push-button operation and a NEMA 4 type enclosure. When alarm conditions are met, low/high alarm visual indicators alert users to gas hazards.

A number of output options are available that allow the AirAwareTM to communicate to external controllers or control external audible/visual alarms. All AirAwareTM units are ModBus enabled for digital communication back to a PLC or DCS system. An optional 4-20 mA output is also available to connect the AirAwareTM to almost any control device. Relays can also be added to turn on fans or warning sirens, or to shut down a process. Standard operating power is 12-24 VDC for the AirAware, while a 120 VAC power supply option is available for convenient plug-in monitoring applications. Configure your AirAwareTM to match your needs, adding options such as on-board audible alarm for maximum attention, or a vanity plate to hide the display. The AirAwareTM is covered by a one-year warranty and carries CSA approval for non-hazardous locations.

Technical Specifications

Case:

NEMA 4 type, General purpose indoor use. Electroplated for RFI protection

Dimensions:

18.29 cm x 14.22 cm x 4.06 cm (7.2′′ x 5.6′′ x 1.6′′ )

Weight:

454 g (16 oz)

Sensor Type:

Electrochemical

Measuring Ranges:

Carbon Monoxide, Hydrogen Sulfide – 0 to 999 ppm in 1 ppm increments
Nitric Oxide – 0 to 999 ppm in 1 ppm increments
Ammonia – 0 to 200 ppm in 1 ppm increments
Oxygen – 0 to 30% by volume in 0.1% increments
Sulfur Dioxide, Nitrogen Dioxide – 0.2 to 99.9 ppm in 0.1 ppm increments
Chlorine – 0.2 to 50 ppm in 0.1 ppm increments
Hydrogen Chloride – 0.2 to 30 ppm in 0.1 ppm increments

Power Source (Run Time):

12-24 VDC (110 AC adapter optional with North American plug)

Temperature Ranges:

-20°C to 50°C (-4°F to 122°F ) typical, consult factory for gas specific temperature ranges

Humidity Range:

Oxygen – 0-99%
Ammonia, Carbon Monoxide, Hydrogen Sulfide, Nitrogen Dioxide, Sulfur Dioxide – 15-90%

Approvals:

CSA – C.22.2 No. 205-M 1983 (non-hazardous locations); CE (pending)

Warranty:

One year, including sensor

CSA